Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
40 Equipment Manual, 07.2021, A5E37775406-11-76
2.4 Operating displays and signaling
Multi-color LEDs at the front of the device indicate the operating state of the device and the
operating state of the outputs.
Meaning of the LEDs
The LED is shown using symbols:
LED off
LED is lit
LED flashes in the inter-
val:
0.1 seconds on/ 0.1 seconds off
0.25 seconds on/ 0.25 seconds off
0.5 seconds on/ 0.5 seconds off
1 second on / 1 second off
5 Hz
2 Hz
1 Hz
0.5 Hz
2.4.1 SITOP UPS1600
2.4.1.1 LEDs
LEDs Labeling, just the same as at the hous-
ing
Description
LED 1
O.K./BAT.
Mode DC-USV
LED 2
BAT.> 85 %
Charge state
LED 3
ALARM
Not ready for buffering!
LED 4
BAT.STATUS
Battery status
LED 5
*1)
SF
PROFINET-specific diagnostic displays
LED 6
*1)
RUN
PROFINET-specific diagnostic displays
LED 7
*1)
P2
Connection status Ethernet port 1
LED 8
*1)
P1
Connection status Ethernet port 2
*1)
Only active for … -2AY0
Figure 2-20 Operating displays

Table of Contents