Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP UPS1600 / BAT1600 / UPS1100
30 Equipment Manual, 07.2021, A5E37775406-11-76
2.2.1.4 PROFINET/Ethernet connection
Figure 2-10 PROFINET/Ethernet connection
The Ethernet interface corresponds to the standard full duplex up to 100 Mbit/s electrical
(100BASE-TX) according to IEEE 802.3.
Properties of the Ethernet interface:
Transfer rate 10/100 Mbit/s
Two RJ45 sockets, i.e. integrated switch, for RJ45 connector
Cable type 100Base-TX (CAT5)
Autonegotiation
Auto-crossover communication via TCP/IP and PROFINET
The strain relief (see Section PROFINET/Ethernet connector (Page 189)) is implemented using
a Siemens IE FastConnect RJ45.
The physics of the Ethernet interface is implemented so that PROFINET IO according to
standards IEC 61158 and IEC 61784-2 is possible. For PROFINET, conformance class B must be
maintained as a minimum.
The Ethernet/PROFINET interface permits:
Configuration and monitoring using the SITOP Manager
Monitoring via the Web server
Integration and communication of the DC-UPS with other automation components from
Siemens and the open environment, e.g. IPC, PLC, HMI, OPC UA
Firmware update of the device via SITOP Manager, web server or STEP 7