EasyManua.ls Logo

Siemens SITOP UPS1100 - Sitop Bat1600

Siemens SITOP UPS1100
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
31
2.2.2 SITOP BAT1600
The power cables to the UPS module and to additional battery modules are connected at
power terminals . Refer to the diagram in Section "SITOP BAT1600 (Page 22)". The data
cables to the UPS module and to additional battery modules are connected at communication
terminals . See also Chapter Installation (Page 211).
Figure 2-11 Power terminals / communication terminals
NOTICE
Material damage
It is not permissible that the "+" and "-" power terminals are connected to the "0V", the 0V
busbar or "GROUND".
Note
Use cables with the same length and the same cross
-section.
Dimension the power cables
corresponding to the fuse in the battery module.
The fuse should only be inserted in the fuse holder when commissioning the device.
See Connecting SITOP BAT1600 battery modules to the UPS module (Page 213)
Connections and terminal designations
Power terminals "-" and "+"
Plug-in terminal each with a screw connection
Communication terminals "COM2", "COM1"
Plug-in terminal each with a screw connection

Table of Contents

Other manuals for Siemens SITOP UPS1100

Related product manuals