Safety, approvals, EMC
9.2 Test voltage
SITOP UPS1600 / BAT1600 / UPS1100
254 Equipment Manual, 07.2021, A5E37775406-11-76
9.2 Test voltage
Figure 9-1 Test voltage diagram
Only applicable for UPS1600 with PROFINET (-2AY0).
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Test (A)
Connect the input, output, battery connection BAT and signaling contact with one another
and measure with respect to PE.
Test (B)
Connect all PROFINET cables and measure with respect to PE (input, output, battery
connection BAT signal connector and PE are connected with each other)
Table 9- 1 Test voltage
Test time
Input, output, BAT ↔ PE (A)
PROFINET ↔ PE (B)
Type test
60 s
700 V DC
2200 V DC
60 s
500 V AC
1500 V AC
Production test
1 s
200 V DC
1 s
140 V AC
Field test
1 s
200 V DC
2200 V DC
1 s
140 V AC
1500 V AC
Remark:
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: < 100 mA