SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
211
Note
When installing the devices, the relevant country
-specific regulations must be complied with.
V supply voltage must comply with SELV (ES1) in accordance with EN62368-1 and
Only qualified personnel are allowed to install the device/system and set it into operation.
It is not permissible that the connections are attached or detached in operation.
Note
for SITOP BAT1600 and SITOP UPS1100
It is recommended that the batteries are only stored fully charged.
The lead acid batteries are fully charged when the device is delivered.
The LiFePO4 battery SITOP UPS1100 (5
Ah) is only supplied, charged up to a maximum of
% of the rated charge (to comply with transport regulations).
For air freight, the LiFePO4 battery of the SITOP UPS1600 battery module (2.5
Ah and 7.5
Ah)
is only charged up to maximum of 30
%; for other transport types, up to 100 %.
lf-discharge rate of the batteries is approx. 3%/month for a temperature of 20° C. This
value is temperature dependent and becomes more unfavorable for an increasing
temperature, and more favorable for a decreasing temperature.
The fuse should only be inse
rted in the fuse holder when commissioning the device.
When storing SITOP BAT1600 / SITOP UPS1100 battery modules in completely wired/cable
systems (with SITOP UPS1600 and fuse inserted in the SITOP BAT1600 / SITOP UPS1100) it
should be noted that an addit
ional discharge current (leakage current) flows.
Ah is only recommended in conjunction with SITOP UPS1600 10 A.
Ah is only recommended in conjunction with SITOP UPS1600 20 A or less.
Ah, 12 Ah, 38 Ah is only recommended in conjunction with SITOP
A or less.
Ah is only recommended in conjunction with SITOP UPS1600 10 A.
Ah, 3.2 Ah and 5 Ah are only recommended in conjunction with SITOP
When using battery modules without Energy Storage Link, it must be ensured that the
selected batteries match the data of the SITOP UPS1600 (static and dynamic load current,
charge current).