Overview
The DC UPS modules supplement 24 V SITOP power supply units for interruption-free rated
currents of up to 40 A from SITOP BAT1600 and SITOP UPS1100 battery modules, which are
based on maintenance-free lead-gel or LiFePO4 batteries. With its integrated electronics,
SITOP UPS1600 automatically detects the battery type and charges it with the optimum
temperature-controlled charging characteristic curve. The intelligent battery management
monitors all relevant data, also for parallel-connected battery modules. The battery status and
various actual values, for example voltage and current, are output via the Ethernet/PROFINET
and USB interfaces. Thanks to the integrated web server, remote diagnosis is also possible.
The low profile SITOP UPS1600 DC-UPS module provides a dynamic overload behavior, e.g. to
switch on industrial PCs. The high charge current quickly restores the buffer readiness after a
supply system failure. And for the deployment in stand-alone operation, the UPS can be
activated from the battery for missing supply system voltage, e.g. to start the generators.
The key benefits of the product include:
Compact SITOP UPS1600 24 V/10 A, 20 A and 40 A DC-UPS modules with digital
inputs/outputs, optional with USB or two port Ethernet/PROFINET interfaces
Battery modules SITOP BAT1600 24 V/3.2 Ah, 12 Ah, 38 Ah with lead-gel batteries and
SITOP BAT1600 24 V/2.5 Ah, 7.5 Ah with LiFePO4 batteries as well as SITOP BAT1600
Battery Monitor are part of the 38 Ah battery module
24 V/1.2 Ah, 2.5 Ah, 3.2 Ah, 7 Ah and 12 Ah SITOP UPS1100 battery modules with
maintenance-free lead-gel batteries or 5 Ah with LiFePO4 batteries and integrated
electronics
Intelligent battery management with automatic detection of the battery modules, and
selection of the optimum temperature-controlled charging characteristic; monitoring
operational readiness, battery feeder cable, aging and charge status
All diagnostic data and alarm messages are available via USB and Ethernet/PROFINET
Supports high dynamic overload capability: 3-fold rated current for 30 ms and 1.5-fold
rated current for 5 seconds per minute
High charge currents