Mounting position, mounting clearances
6.2 SITOP BAT1600
SITOP UPS1600 / BAT1600 / UPS1100
206 Equipment Manual, 07.2021, A5E37775406-11-76
6.2.2 Other mounting positions
Note
In the case of mounting positions that deviate from the standard mounting position, reduced
mechanical resistance of the devices
against vibration and shock must be expected.
Particularly when installing on a vertically fastened DIN rail, additional measures may be
required, e.g. to prevent the device from slipping on the DIN rail.
LFP can be installed in any position.
Lead-gel batteries must not be installed upside down.
The 38 Ah device may only be mounted in the horizontal position, (see Figure 5-8 Installation
6EP4137-0GE00-0AY0 (38 Ah Pb) (Page 194))
The subsequent mounting position is forbidden for the SITOP BAT1600 3.2 Ah: