Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
45
Contact rating:
30 V AC/0.5 A 60 V DC/0.3 A 30 V DC/1 A
Note
From the instant in time when the SITOP UPS1600 is switched over into the buffer mode, for
the evaluation, instead of the expected buffer current, the actually measured buffer current is
used. As a consequence, the status of the LEDs and the relay can also change.
Note
The value assumed for the buffer time is based on the battery being in a new state.
2.4.2 SITOP BAT1600
No.
Labeling
Signal type
Signaling
O.K.
LED
Device status
Meaning of the LED colors for buffering:
Green
buffer readiness
Yellow
buffer mode endangered
Red
buffer mode not possible