Technical data
8.1 Input data
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
237
8.1.3 SITOP UPS1100
Charge current
The charge current is limited by the maximum permissible charge current of the SITOP
UPS1600 (see Chapter SITOP UPS1600 (Page 238))
When a battery module is connected, the charge current is max. 0.3 CA.
For several battery modules connected in parallel, the charge current is max. 0.3 CA
multiplied by the number of batteries connected in parallel.
Recommended end-of-charge voltage (standby use), dependent on the battery
temperature
6EP4131-0GB00-0AY0 (1.2 Ah)
6EP4133-0GB00-0AY0 (3.2 Ah)
6EP4134-0GB00-0AY0 (7 Ah)
6EP4135-0GB00-0AY0 (12 Ah)
6EP4132-0GB00-0AY0 (2.5 Ah) 6EP4133-0JB00-0AY0 (5 Ah)
At -10 °C
28.0 V
28.0 V
28.8 V
At 0 °C
28.0 V
28.0 V
28.8 V
At 10 °C
27.8 V
27.8 V
28.8 V
At 20 °C
27.3 V
27.3 V
28.8 V
At 30 °C
26.8 V
26.8 V
28.8 V
At 40 °C
26.6 V
26.6 V
28.8 V
At 50 °C
26.3 V
26.3 V
28.8 V
At 60 °C
-
26.0 V
-
Note
The 5
Ah SITOP UPS1100 battery module with LiFePO4 batteries can only be used in
conjunction with SITOP UPS1600 from software version V2.1.