Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
168 Equipment Manual, 07.2021, A5E37775406-11-76
Display name
Data type
Definition
Description
DeviceInputCurrent
Float
AnalogItemType
Measured input current of SITOP UPS1600
DeviceInputVoltage
Float
AnalogItemType
Input voltage
DeviceInputVoltageOK
Boolean
PropertyType
Input voltage has exceeded the configured threshold volt-
age. Connected devices are powered with the input supply.
DeviceLoadCurrent
Float
AnalogItemType
Measured output current of SITOP UPS1600
DeviceMaxCurrent
Float
AnalogItemType
Maximum output current supported by the SITOP UPS1600
DeviceOutputCurrent
Float
AnalogItemType
Measured output current of SITOP UPS1600
DeviceOutputVoltage
Float
AnalogItemType
Measured output voltage
DeviceP1LinkLed
Object
Sitop_1600_
LedType
Status of LED "P1"
DeviceP2LinkLed
Object
Sitop_1600_
LedType
Status of LED "P2"
DeviceRunLed
Object
Sitop_1600_
LedType
Status of LED "RUN"
DeviceSFLed
Object
Sitop_1600_
LedType
Status of LED "SF"
DeviceSWSettings
Valid
Boolean
PropertyType
This object provides information about whether the SW
parameters or the parameters at the rotary switches are
used. The corresponding setting should be made at the rota-
ry coding switch for the buffer threshold.
DeviceStateLed
Object
Sitop_1600_
LedType
Status of LED "OK" Device status
DeviceTemperature
Sbyte
AnalogItemType
Device temperature
DeviceTotalOperating
Time
UInt32
AnalogItemType
Battery-specific data: Total time for which battery was in
buffer mode during its service life
3.10.6.6 ActualUpdateState
Display name
Data type
Definition
Description
UpdateProgress
Integer
PropertyType
Update progress
UpdateState
Enumeration
MultiState
DiscreteType
Update status
3.10.6.7 Alarm
Display name
Data type
Definition
Description
AlarmBattery
ConnectionBroken
Boolean
PropertyType
Connection to battery interrupted - check connection and
fuse
AlarmBattery
ConnectionHigh
Resistive
Boolean
PropertyType
High-resistance connection to battery - check battery power
cable
AlarmBatteryDeep
Discharge
Boolean
PropertyType
Battery is deep discharged - no buffering possible.
AlarmBatteryDeep
DischargeNoCharging
Possible
Boolean
PropertyType
Battery is deep discharged - replace battery.
AlarmBatteryDefect
Boolean
PropertyType
Battery defective - check fuse and battery voltages.