EasyManua.ls Logo

Siemens SITOP UPS1100 - Environmental Conditions

Siemens SITOP UPS1100
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
257
Environmental conditions
10
6EP4134-3AB00- … (10 A)
6EP4136-3AB00- … (20 A)
6EP4137-3AB00- … (40 A)
Ambient temperature
-25 ... 70 °C for natural convec-
tion (self convection)
-25 ... 60 °C for natural convec-
tion (self convection)
15 A (derating) at 60° ... 70° C
-25 ... 60 °C for natural convec-
tion (self convection)
30 A (derating) at 60° ... 70° C
Tested according to:
EN 60068-2-1 Cold
EN 60068-2-2 Dry heat
EN 60068-2-78 Humid heat, constant
EN 60068-2-14 Temperature change
Remark: The service life of the UPS1100 battery modules (decrease to 50 % of the original capaci-
ty) depends on the battery temperature, at approximately 20 °C: 4 years, 30 °C: 2 years, 40 °C: 1
year
Transport and storage
temperature
-40 ... 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 Cold
EN 60068-2-2 Dry heat
EN 60068-2-30 Humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
Degree of pollution
2
Mechanical
stress in operation
Tested according to:
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 9 Hz
1 g acceleration in the range 9 - 150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms
Damaging gases
Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
1080 - 795 hPa (-1000 - 2000 m)
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5 % / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 6-20 Altitude derating (Page 209)
Storage:
1080 - 660 hPa (-1000 - 3500 m)

Table of Contents

Other manuals for Siemens SITOP UPS1100

Related product manuals