Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
87
3.4.11 Restore factory settings
A reset to the factory settings deletes all configurations of the PROFINET interface saved in
the SITOP UPS1600 and restores the factory settings. This affects, for example:
IP address
Device name
The parameter values for SITOP UPS1600 and the energy storage device are kept.
Proceed as follows to reset the SITOP UPS1600 factory settings:
1. Select SITOP UPS1600 in the Network view and change to the Device view.
2. Click on "Go online".
3. In the SITOP UPS1600 shortcut menu, select "Online & diagnostics".
4. In the "Functions" folder, select the "Reset to factory settings" group.
5. Click on the "Reset" button.
6. Respond to the confirmation prompt with "OK".