Engineering and remote access
3.11 SNMP Agent
SITOP UPS1600 / BAT1600 / UPS1100
180 Equipment Manual, 07.2021, A5E37775406-11-76
3.11 SNMP Agent
An SNMP agent is integrated in SITOP UPS1600 corresponding to the PROFINET specification.
Via this SNMP agent, a network management system (e.g. SINEMA server) can call up
administrative information about the unit. Corresponding to the SNMPv1/SNMPv2 notation,
this information is summarized in the "system" group
(iso(1).org(3).dod(6).internet(1).mgmt(2).mib-2(1).system(1)).
The following example illustrates the associated nomenclature:
Name
Access
Explanation
Default setting
sysDescr
Read
A character string with the following content is
used: "[<Supplier>, <Product family>, <Product
name>, <Order number>, <HwVersion>,
<FwVersion>, <Serial number>]"
"Siemens, SITOP Power, UPS1600,
6EP4136-3AB00-2AY0, HW: Ver-
sion 7, FW: Version V02.04.00,
SQ6H4BNL7F5G"
sysObjectID
Read
Object identification of the automation compo-
nent
".0.0"
sysUpTime
Read
Time in 1/100 s since switching on
-
sysContact
Read/write
Text identifier of the contact person for this
unit, as well as information to make contact
with this person. Is provided by the network
manager.
-
sysName
Read/write
A name assigned by the administrator for this
unit
-
sysLocation
Read/write
The physical location of this unit. Is provided by
the network manager.
-
sysServices
Read
A value, which specifies the set of services that
this unit offers. The value is coded as the sum of
the individual service identifiers.
"76" (application + end-to-end +
internet)

Table of Contents