Engineering and remote access
3.9 Web server
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
137
The individual columns contain the following information:
Name: A descriptive name of the alarm identifier
Date and time: Time, degree of severity and date when the alarm comes and goes
Incoming/outgoing:
incoming: Occurrence of the alarm event
outgoing: Rectification of the alarm event
3.9.6.2 View the data of the SITOP UPS1600 (basic device)
1. Select menu "Diagnostics".
2. Select the "Base unit" entry under "Operating data" in the navigation.
Here, you can find the following information:
Data of the SITOP UPS1600:
Article number
Serial number
SW revision
Hardware revision
Operating state (normal or buffer mode)
Status of the charging unit
Buffer readiness
Remaining buffer time
Note
From the instant in time when the SITOP
UPS1600 is switched over into the buffer mode,
the buffer current actually measured is used to determine the expected buffer time
instead of the expected buffer current.