Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
41
States of the LEDs
LED 1 (O.K./BAT.)
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
DC-UPS defect (severe hardware fault)
Flashing yellow
(0.25/0.25)
Critical temperature identified, overtemperature or overvoltage at the input
LED 2 (BAT.> 85%)
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
Battery module charge state < 10 %
Flashing green
(0.25/0.25)
10 % < battery module charge state < 85 % or firmware update
(1/1)
85 % < battery module charge state < 100 %
Battery module charge state = 100 %
The LED and the relay contact (see Chapter Relay outputs (Page 44)) have two meanings:
1. If no additional settings have been made, then the previous LED signaling applies.
2. If an expected buffer current and a buffer time are set under the hardware configuration,
then the LEDs and the relay contact serve as an indicator when buffering is possible with the
two parameters – or is no longer possible.
From the instant in time when the SITOP UPS1600 is switched over into the buffer mode, for
the evaluation, instead of the expected buffer current, the actually measured buffer current is
used. As a consequence, the status of the LEDs and the relay can also change.