Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
110 Equipment Manual, 07.2021, A5E37775406-11-76
0x0005: Battery information parameters (reading)
Number of connected battery modules. Here, only SITOP BAT1600
or SITOP UPS1100 battery modules (SITOP system batteries) are
Batt 1: Standby time [1 s]
Batt 1: Buffer time [1 s]
Batt 1: Total charging current
[1 mAh]
Total charge level (battery-specific data): Total charge within the
service life of the SITOP UPS1600.
Batt 1: Total culled current [1 mAh]
Total charge level used (battery-specific data): Total discharge over
the service life of the SITOP UPS1600.
"End-of-charge voltage": Battery voltage when charging changes to
trickle charging. The energy storage device is then charged up to
Batt 1: Charge current [1 mA]
Charge current: Current magnitude used to charge the connected
battery modules during the constant current charging phase.
Batt 1: Battery capacity [0.1 Ah]
Battery capacity: Total battery capacity of all energy storage devic-
es connected to the SITOP UPS1600.
Batt 1: Stop buffering voltage
[0.01 V]
Battery voltage, which when fallen below, buffer mode is exited
(stop buffering voltage).
Batt 1: Minimal temperature [1 °C]
Lowest specified operating temperature of the SITOP BAT1600 or
SITOP UPS1100 battery module being used
Batt 1: Maximal temperature [1 °C]
Highest specified operating temperature of the SITOP BAT1600 or
SITOP UPS1100 battery module being used
Order number (Article number).
Batt 1: Manufacturing date
Batt 1: Calculated battery health
Calculated battery health
Battery Module Ident Number
Batt 2: Standby time [1 s]
Batt 2: Total charging current
[1 mAh]
Total charge level (battery-specific data): Total charge within the
service life of the SITOP UPS1600.
Batt 2: Total culled current [1 mAh]
Total charge level used (battery-specific data): Total discharge over
the service life of the SITOP UPS1600.
"End-of-charge voltage": Battery voltage when charging changes to
trickle charging. The energy storage device is then charged up to
Batt 2: Charge current [1 mA]
Charge current: Current magnitude used to charge the connected
battery modules during the constant current charging phase.
Batt 2: Battery capacity [0.1 Ah]
Battery capacity: Total battery capacity of all energy storage devic-
es connected to the SITOP UPS1600.