Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
114 Equipment Manual, 07.2021, A5E37775406-11-76
0x0006: Device information parameters (reading)
MLFB/order number (Article number)
0x0007: Hardware settings parameters (reading)
Buffer time: After the selected buffer time has expired, the SITOP
UPS1600 switches off the load output. The actual buffer time that
can be achieved depends on the connected loads and energy stor-
Buffer threshold [0.01 V]
Connection threshold: Switching voltage for buffering. Buffering is
active below this value.
Activate or deactivate buffer mode. This setting is only accepted by
the SITOP UPS1600 in the Remote Enable (REN) operating mode.
Enable reset: If, during buffer mode, the input voltage becomes
available again, then the output of the SITOP UPS1600 is switched
off for a selectable time in order to reset connected loads.
Start from battery: Setting at the signal terminal for function "Start
from battery".
Profile of the selected battery: The battery charging behavior is set
at the signal terminals. The setting is only used, if the SITOP
UPS1600 is not in the "Remote Enable" (REN) mode.
0x0008: Buffering parameters (reading/writing)
Expected buffer current [0.1 Ah]
from V2.0 and higher
Expected buffer current: Estimated average load current during
buffer mode.
0x0009: Maintenance parameters (reading/writing)
Resistor test interval [1 h] from
V2.1