Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
122 Equipment Manual, 07.2021, A5E37775406-11-76
Battery Module Ident Number
0x0020: State information (reading)
Remaining buffer time [1 s]
Probable remaining buffer time. The remaining buffer time is cal-
culated based on the present battery charge and the average cur-
rent over a 10 minute period.
Total operating time [1 h]
Total calculated battery capacity
[0.1 Ah]
Total calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Calculated battery 1 capacity
[0.1 Ah]
Battery 1: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Calculated battery 2 capacity
[0.1 Ah]
Battery 2: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Calculated battery 3 capacity
[0.1 Ah]
Battery 3: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Calculated battery 4 capacity
[0.1 Ah]
Battery 4: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Calculated battery 5 capacity
[0.1 Ah]
Battery 5: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Calculated battery 6 capacity
[0.1 Ah]
Battery 6: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Input voltage: Measured rms value of the supply voltage at the
input of the SITOP UPS1600.
Current measured at the input of the SITOP UPS1600.
Voltage measured at the output of the SITOP UPS1600.
Load current measured at the output of the SITOP UPS1600.
Measured charge current [1 mA]
Measured battery charge current of the SITOP UPS1600.
Measured battery voltage of the connected battery modules
Load current measured at the output of the SITOP UPS1600.
Voltage used to charge the battery during the constant-current
charging phase
Valid configuration: Indicates whether the software parameters or
the parameters at the rotary coding switch are used. The corre-
sponding setting should be made at the rotary coding switch for
Number of connected battery modules. Here, only SITOP BAT1600
or SITOP UPS1100 battery modules (SITOP system batteries) are
Battery 1 change recommended
Battery 1: Battery replacement recommended: The battery capacity
is not sufficient for the defined buffer time.
Battery 2 change recommended
Battery 2: Battery replacement recommended: The battery capacity
is not sufficient for the defined buffer time.