Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
124 Equipment Manual, 07.2021, A5E37775406-11-76
0x0041: Web server parameters (reading/writing)
Data
Description
Data type
WebserverEnabled
Activating/deactivating the web server of the SITOP UPS1600:
0: disable
255: enable
Unsigned8
AutoReloadEnabled from V2.1
Enable/disable automatic update:
0: disable
255: enable
Unsigned8
ReloadTime from V2.1
Update interval:
0: Off
5: 5s
10: 10s
20: 20s
30: 30s
60: 60s
Unsigned8
AutoLogout from V2.1
Enable/disable automatic logoff:
0: disable
255: enable
When automatic logoff is activated, the logged on user ("Guest" or
"Admin") is automatically logged off when the SITOP UPS1600 web
server is inactive for 15 minutes.
Unsigned8
HttpAccessEnable from V2.1
Enable/disable HTTP access:
0: disable
255: enable
Unsigned8
Fill byte(s) from V2.1
-
Unsigned8