Engineering and remote access
3.9 Web server
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
153
Energy storage
"Energy storage" has two different areas that depend on the battery type being used. First
select whether you are using a SITOP UPS1100 or SITOP BAT1600 battery module or some
other energy storage.
Using a SITOP BAT1600 or SITOP UPS1100 battery module
No additional parameterization.
Using a different battery module
Parameter
Value range
Default setting
Battery type
0 - 1
0
Typical ambient temperature
-70 - 100 °C
40 °C
Battery capacity
0.1 - 3,200 Ah
10 Ah
End-of-charge voltage at 20 °C
24 - 30 V
27.3 V
Temperature coefficient
0 - 200 mV/K
36 mV/K
Duration of the constant floating voltage charging phase
0 - 720 h
12 h
Charge current
0.001 - 3 or 4 or 5 A
0.3 A
Start preserve charge voltage
23 - 30 V
25.20 V
Stop buffering voltage
18 - 23 V
18.50 V
Faulty battery voltage
1 - 18 V
6 V
Battery type
Make/type of battery: Pb … lead-gel battery, pPb … pure lead battery
Typical ambient temperature
Typical ambient temperature of the battery in operation