Environmental conditions
SITOP UPS1600 / BAT1600 / UPS1100
260 Equipment Manual, 07.2021, A5E37775406-11-76
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
6EP4135-0GB00-0AY0
6EP4132-0GB00-0AY0
(2.5 Ah)
6EP4133-0JB00-0AY0
(5 Ah)
• EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
• 1080 - 795 hPa (-1000 - 2000 m)
• Operation at altitudes of 4000 m above sea level and
higher is not permissible (exception, 2.5 Ah).
• Operation at installation altitudes of 2000 - 6000 m
above sea level:
output power derating of -7.5 % / 1000 m - or
reduction of the ambient temperature by5 K / 1000 m
see Figure 6-20 Altitude derating (Page 209)
Storage:
1080 - 660 hPa (-1000 - 3500 m)