Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
67
A menu opens with the available controllers.
2. Select a controller in the menu.
3. Select the connection between the controller and SITOP UPS1600.
4. Make the required settings in the "Network data".
5. Double-click on SITOP UPS1600 to display it in the device view.
6. Select the PROFINET interface.
7. Under "Ethernet addresses" in the inspector window enter the IP address of the
SITOP UPS1600, which was already assigned in the TIA Portal.
You have assigned a controller to the SITOP UPS1600.