Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / BAT1600 / UPS1100
74 Equipment Manual, 07.2021, A5E37775406-11-76
Charging
Parameter
Value range
Default setting
Deactivate charging
Yes / No
No
Maximum permissible charge current
3,000 mA / 4,000 mA / 5,000 mA
3,000 mA / 4,000 mA / 5,000 mA
Deactivate charging
Shut down battery charging
Maximum permissible charge current
Max. permissible current to charge the battery
Energy storage
The parameters in Section "Energy storage" are dependent on the battery type used.
Configure the type of the battery module you are using SITOP BAT1600, SITOP UPS1100 or
third-party battery.
Parameters when using a SITOP BAT1600 or SITOP UPS1100 battery module
Parameter
Value range
Default setting
Battery module
Drop-down menu with the SITOP BAT1600, SITOP UPS1100 battery modules
or third-party battery saved by the HSP.
-
Number of modules
1 - 6
1
Total capacity
0 - 228 Ah
-
Battery module
Type of SITOP BAT1600, SITOP UPS1100 battery modules or third-party battery
Number of modules
Number of installed modules.
Total capacity
Total capacity of the installed battery modules.