3-2
When a fault or isolate condition or is detected by the 4100, the panel does the following to
indicate the presence of the condition.
Yellow indicator, labeled “FAULT” or “ISOLATE” flashes
Tone-alert (piezo buzzer) sounds steady
The alphanumeric display on the interface panel indicates the fault or isolate condition, as
shown below.
** FAULTS **
EXT BELL
ISOLATE
ALARMWARN SYS
FIREFIGHTER FACILITY
ISOLATEFAULT
ALARMS = Ø
EXT BELL
ISOLATE
WARN SYS
ISOLATE
PREV
NEXT
ACK ISOLATERESET
Press <FAULT ACK> to review
ISOLATIONS = Ø FAULTS = 1
POWER
Figure 3-1. Interface Panel Showing Fault Condition
The first step in managing a fault or isolate condition is to acknowledge the condition.
Acknowledging a fault or isolate condition does two important things:
It records the time and date at which you observed the presence of the condition and
stores that information in the system’s historical log.
When you press the <FAULT ACK> or <ISOLATE ACK> key, the system displays
specific data on the location of the condition.
Note: Isolate conditions typically auto-acknowledge and most times do not require
manual intervention. In some cases, however, you may be required to manually
acknowledge the isolate condition as described in this section.
It is important to understand that the 4100 can be configured with either Global or Individual
Acknowledge. These options function as follows:
Global Acknowledge. When global acknowledge is enabled, one press of the
<FAULT ACK> or <ISOLATE ACK> key acknowledges every point currently reporting
a fault or isolate condition.
Individual Acknowledge. If individual acknowledge is enabled, the <FAULT ACK>
or <ISOLATE ACK> key must be pressed repeatedly to individually acknowledge each
fault or isolate condition.
The <FAULT ACK> and <ISOLATE ACK> keys are located under the cover of the panel. If
these keys are passcode-protected (by default, they are not), you cannot use these keys to
acknowledge fault or isolate unless you have the required passcode.
Continued on next page
Acknowledging Fault or Isolate Conditions
How the 4100
Indicates the
Presence of a Fault
What Acknowledge
Does
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes

Related product manuals