9-2
Follow these steps to set the time and date on the panel.
1. Press the <MENU> key. The following appears on the alphanumeric display.
Press <NEXT> or <PREVIOUS> to scroll
Change Access Level
2. Press the <NEXT> key. The following appears.
Press <NEXT> or <PREVIOUS> to scroll
Set Time and Date
3. Press the <ENTER> key. The current time and date information displays, along with
instructions:
Press <FUNCTION> to change time and date
0:09:23 FRI 01 JAN 88
4. Press the <FUNCTION> key. The cursor, current time and date along with function key
definitions are displayed:
F1=Left F2=Right F3=Inc F4= Dec
0:09:23 FRI 01 JAN 88
NOTE: The cursor is positioned under the hour. Function key F1 will move the cursor left.
Function key F2 will move the cursor right. Function key F3 will increase the
data above the cursor . Function key F4 will decrease the data above the cursor.
Set the time 1 minute ahead of source time.
5. Use the required function key to position the cursor under the data to be changed (hour,
minutes, seconds, date of month, month, and year). Day of week is set by the system.
Time entered does not start until the <ENTER> key is pressed.
6. Use Function key F3 or F4 to increase or decrease data, as required.
When time and date are correct, press the <ENTER> key. The display will show
the updated time and date. The time entered will not start until the <ENTER> key is
pressed.
Press <FUNCTION> to change time and date
22:04:46 WED 27 SEP 00
Setting Time and Date
Procedure
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes

Related product manuals