4100-0110 MAPNET® TRUEALARM™ Addressable Loop
Module
Up to 127 MAPNET Addressable devices or
TrueAlarm Analog Sensors
Up to 10 MAPNET Loop Cards per 4100 system
Supports MAPNET Short Circuit Line Isolator
Modules
4100-0304 Remote Unit Interface Module
Provides a supervised serial communications
channel to remotely located distributed Miniplex®
Transponders and LCD Annunciators
Up to 32 distributed Miniplex® Transponders and/or
LCD Annunciators per 4100 system
4100-3024 24 Relay Input / Output Relay Motherboard
24 CPU controlled relays
Each of the 24 relays can be individually configured
as either an input or an output
SPST contacts rated for 0.5 amps @ 24VDC or
30VAC
4100-0301 64/64 LED / SWITCH Controller
Interfaces up to 64 LEDs and 64 switches to the
master controller for front panel annunciation
4100-0111 Mapnet 2 Quad Isolator Module
The Mapnet Quad isolator provides fault tolerance
and electrical isolation capabilities to 4100 Mapnet
lines. The fault tolerance is twofold: loop open circuit
(Class A operation) and short circuit disconnection
4100-0157A Provides a 24 VDC, 12 Amp Power Supply with
integral 4 Amp battery charger.
4100-0302 24 Point Graphic Input / Output Module
This card provides up to 24 inputs or outputs to be
programmed and connected into the system. These
24 points can be split up into any combination of inputs
or outputs to suit individual system needs
.
4100-4321 6 Supervised Relay Module
Each card provides 6 circuits of Style Y (class B) signal
circuits All 6 circuit also have two power inputs, one for
every three signal circuits.
Every signal circuit is supervised for ground faults,
opens and line-to-line shorts
4100-0154 VESDA HLI Module
Provides a high level interface to control up to 30
VESDA LaserPlus, Laser Compact , Mini scanners
or E70D units. The module occupies a Mapnet
channel address and requires a VESDA Net
Interface unit to connect to the VESDA units
Continued on next page
4100 Specifications, Continued
Expansion Modules,
(continued)
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes