SKOPE TME/SKT ActiveCore
Troubleshooting
Service Manual
Cabinet and Refrigeration Unit
For problems with the cabinet and refrigeration unit use the following table.
Table 35: Cabinet and unit troubleshooting
Problem Possible cause Repair
Cabinet not operating
No controller display
Loss of power supply Check mains power supply.
Loose plug in electrics box Check all plugs in electrics box are connected correctly.
High pressure event Service unit and reset pressure switch.
Sign and/or Interior
lights not on.
Electronic controller displays
ECO indicating the fridge is in
Energy Saving mode.
Switch the light on while keeping the fridge in Energy
Saving mode by pressing the light button on the electronic
controller faceplate.
Change the fridge into Normal mode by pressing and
holding the Day-Night button on the electronic controller
faceplate, or hold the door open for ten seconds.
Light switched off. Switch light on via button on the electronic controller
faceplate.
Electronic controller displays E3
indicating a refrigeration system
error.
See “Controller Alarms” on page 70.
Failed LED light. Service light.
Sign and interior lights
will not switch off.
Fridge in Cold Climate
Protection (CCP) mode.
It is not possible to turn the lights off when the fridge is in
CCP mode. Wait for the fridge temperature to raise as
necessary and then switch the lights off.
Excess noise vibration Refrigeration pipes transferring
vibration into unit
Re-align pipes.
Frozen evaporator coil Setpoint is too cold Check and raise (see page 16).
Control probe fault Check and replace control probe.
Evaporator probe fault. Check and replace evaporator probe.
Controller fault Replace controller.
Short of refrigerant Perform refrigeration system diagnostics (see page 32) and
service as required.
Compressor pumping fault. Check compressor and replace if necessary.
Power consumption is
higher than expected
Unit operating too hot Clean the condenser.
Ensure the cabinet has good ventilation around the
refrigeration unit.
Ensure the cabinet is within the maximum operating
temperature.
Cabinet door is opened
excessively
Ensure door is closed more often.
Product too cold Raise setpoint
Product is too warm. Frequent door opening. Limit door openings.
Recently loaded Allow time for the product to cool down.
Door not closing properly. Check and clean door gasket.
Refrigeration unit operating too
hot.
Excessive door opening or
refrigeration heat load.
Ensure the cabinet has good ventilation around the
refrigeration unit.
Ensure the cabinet is within the maximum operating
conditions.
Electronic controller displays
ECO indicating the fridge is in
Energy Saving mode
Switch the fridge to Normal mode via button on electronic
controller faceplate.
Setpoint is too high Lower setpoint.