☐ With all inverters, the parameter Operating mode active power must be set to the value
Active power limitation P via system control (see SunnyExplorer user manual).
☐ You must have the user role Installer or PV System Administrator (see Section13.1,
page120).
Procedure:
1. Select Configuration > PV system properties in the page and menu selection.
2. Select the tab Parameters.
3. Select [Edit].
☑ The menu for parameter settings opens.
4. In the area Limiting of the active power feed-in, select the applicable option:
• If limitation of active power feed-in is not required for your system, select no limiting of
the active power feed-in (default setting).
• If limitation of active power feed-in is required for your system, carry out the following
steps:
– To test whether the limitation of active power feed-in is working in the system, select
the option max. xx kW and enter the value 0. Thus, the SunnyHomeManager
immediately limits the active power when the inverters start feeding into the utility
grid.
– If the grid operator requires limitation to a maximum active power in kW, select the
option max. xx kW and enter the maximum permitted active power in kW.
– If the grid operator requires limitation to a percentage of the nominal PV system
power, select the option Max.xx% of the nominal PV system power and
enter the required percentage.
– If the grid operator requires limitation of the active power feed-in to 0%, select the
option Max. xx% of nominal PV system power and enter the value 0.
5. Select [Save].
☑ The data is being transferred. This can take up to five minutes.
6. To display the active power limitation, select Energy Balance > Current or Energy Balance
> Day in the page and menu selection.
☑ In the diagrams Energy balance - Current and Energy balance - Day, the specified
limitation of active power feed-in is displayed as a red line. If the PV production exceeds
the specified threshold, a blue area is shown above the red line as a maximum, and this
corresponds to the current self-consumption.
12.10 Activating/Deactivating Grid Management Services
The SunnyHomeManager can receive the specifications for grid management services via
Ethernet-based communication. The grid operator can set up this link. You also have to activate grid
management services for the SunnyHomeManager.
12 System Settings
SMA Solar Technology AG
User Manual 115HoMan_Portal-BA-en-20