-64-
No.EX※※-OMX1011
•Digital I/O unit parameters (2)
No.
Parameter
Definition
Item
Content
Default
setting
Parameter
setting range
10
Input or
Output
ON/OFF
counter
Generates error
when the operation
count exceeds the
set value.
4
Enable
Generates an error.
Val: 1 to 65000
5
Channel
Disable
Does not generate an
error.
11
Input or
Output
ON/OFF
counter clear
Clears the Input or
Output ON/OFF
counter to 0. (Refer
to page 131 for the
clear method).
-
-
-
-
1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the
parameter setting.
2: This function is valid only when "Hold/Clear priority" of the system parameter is set to "Via software".
3: Some PLC does not support an idle mode.
4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
5: Times for setting is set value x1000 times.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600-SEN3 and is the answer not in the manual?

SMC Networks EX600-SEN3 Specifications

General IconGeneral
BrandSMC Networks
ModelEX600-SEN3
CategoryI/O Systems
LanguageEnglish

Related product manuals