Error code
LCD message Cause and Troubleshooting
CPU v3.18
and below
CPU v3.19
and above
196 2xC4
Backup init over
voltage
o
External voltage source on backed-up loads when
operating in Backup mode. Disconnect all external
voltage sources on backed-up loads.
o
Inverter internal error. Contact SolarEdge support.
0x2010 Internal CB down
Make sure that the loads do not consume higher
current than the inverter max output current. Open the
inverter Connection Unit and switch the main circuit
breaker to the ON position.
System Warnings
Warningsaredisplayedintheinitialstatusscreenwiththeformat:<WarningX>.Forexample:
V a c [ V ] V d c [ V ] P a c [ W ]
1 . 0 0 . 5 0 . 0
P _ O K : X X X / Y Y Y < S _ O K >
W a r n i n g 8 O N
Thewarningisastatusscreen.Toviewthewarningdescription,presstheLCDbutton.
Thefollowingisalistofsystemwarnings:
Warning #
LCD text Comments and troubleshooting
CPU v3.18xx
and before
CPU v3.19xx
and later
1-4, 6-7
8x66 - 8x69
8x6A - 8x6F
Fan # Failure Clean or replace the fan
5 Turn Switch Off to Configure
Appears when trying to access the
Setup menus during production
8 2x111 Connection Unit Low 9V Battery
Replace the 9V battery in the
Connection Unit. Refer to 9V Battery
Replacement on page 104.
Appendix A: Troubleshooting
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
101

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolarEdge SEAUTO-TX-5000 and is the answer not in the manual?

SolarEdge SEAUTO-TX-5000 Specifications

General IconGeneral
BrandSolarEdge
ModelSEAUTO-TX-5000
CategoryInverter
LanguageEnglish

Related product manuals