Creating an Ethernet (LAN) Connection
ThiscommunicationoptionenablesusinganEthernetconnectiontoconnecttheinvertertothe
monitoringplatformthroughaLAN.
Ethernetcablespecifications:
l Cabletype–ashieldedEthernetcable(Cat5/5ESTP)maybeused
l Maximumdistancebetweentheinverterandtherouter–100m/330ft.
NOTE
If using a cable longer than 10 m / 33 ft in areas where there is a risk of induced
voltage surges by lightning, it is recommend to use external surge protection
devices.
For details refer to: http://www.solaredge.us/files/pdfs/lightning_surge_
protection.pdf. A surge protection device is available from SolarEdge.
https://www.solaredge.com/sites/default/files/rs485_surge_protection_kit_
installation_guide.pdf
If not using surge protection, connect the grounding wire to the first inverter in the
RS485 chain; make sure the grounding wire is not in
contact with other wires. Connect the grounding wire to the grounding bus-bar in
the Connection Unit.
Figure 34: Example of Ethernet connection
To connect the Ethernet cable:
1. RemovetheinvertercoverasdescribedinRemovingtheInverterCoveronpage44.
2. Openthecommunicationgland#1.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to ensure proper sealing.
Le cote interne du gland contient une rondelle qui doit être utilisée pour une bonne étancheïté.
3. Removetheplasticsealfromthelargeopeningthathasacutintherubberfitting.
Chapter 9: Setting Up Communication to the Monitoring Platform
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
75