Function / parameter Description Unit / status
GFMMIN2 Checking the minimum permissible mains fre-
quency (limit 2)
-
GFMMIN2-ENA GFMMIN2 function status Disabled/enabled
GFMMIN2-THR Limit value Hz
GFMMIN2-DLY Trip time s
GFMMAX2 Checking the maximum permissible mains fre-
quency (limit 2)
-
GFMMAX2-ENA GFMMAX2 function status Disabled/enabled
GFMMA X2-THR Limit value Hz
GFMMAX2-DLY Trip time s
AIS Detection of island operation -
AIS-ENA AIS function status Disabled/enabled
AIS-DLY Trip time s
RBCM Monitoring the continuous leakage current -
RBCM-ENA RBCM function status Disabled/enabled
RBCM-THR Maximum permissible leakage current A
RSCM Monitoring the leakage current step value -
RSCM-ENA RSCM function status Disabled/enabled
DCCIM Monitoring the DC component in the AC current -
DCCIM-ENA DCCIM function status Disabled/enabled
DCCIM-THR Maximum permissible DC component in AC current A
DCCIM-DLY Trip time s
Limitation
Functions and parameters of the "Limitation" sub-menu:
Function / parameter Description Unit / status
ACPPL Maximum increase in the active power during grid
connection
-
ACPPL-ENA ACPPL function status Disabled/enabled
ACPPL-MGDT Increase % of Pac nom/
min
ACPPL-INI ACPPL at every start-up Disabled/enabled
ACPPL-RCN ACPPL at start-up after grid disconnection caused
by coupler breaker
Disabled/enabled
ACPL Limitation of active output power -
AC P L-L MT Limit value W
APPL Limitation of the apparent power -
APPL-LMT Limit value VA
OCL Limitation of the output current -
OC L- LM T Limit value A