NOTES RELATING TO CONSOLE LOCATION AND AIR CONDITIONING
• Any item of electronic equipment can be affected by electrostatic discharge. It is considered good practice to avoid
using fully insulating floor coverings in technical areas.
• Air conditioning may sometimes be required; note however, that a cool and dry atmosphere can significantly
increase the likelihood of a build-up of static charge. It is recommended that air conditioning systems are designed
such that the relative humidity does not fall below 30% during periods of operation.
Appendices
AWS δelta Owner’s Manual Appendices Page A-7
DENVIRONMENTAL SPECIFICATION
Temperature Operating: 5 to 30 Deg. C
N
on-operating: -20 to 50 Deg. C
Max. Gradient: 15 Deg. C/Hour
Relative Humidity Operating: 30 to 80 %
Non-operating: 5 to 90 %
Max. Wet bulb: 29 Deg. C (non-condensing)
Vibration Operating: < 0.2 G (3 - 100Hz.)
Non-operating, power off: < 0.4 G (3 - 100Hz.)
Shock Operating: < 2 G (10mSec. Max.)
Non-operating: < 10 G (10mSec. Max.)
Altitude Operating: 0 to 3,000 m
(Above sea level) Non-operating: 0 to 12,000 m