119
➐
➑
© STULZ GmbH – all rights reserved EN/06.2019/G57
C7000 INSTRUCTIONS fOR a/C UNITS
The corresponding commands:
puts unit 3 into standby
switches unit 3 on
The operating status of all units which are assigned to zone 1 is displayed in
the top line. From left to right the operating states of the units with the bus
address from 19 to 0 are displayed. 0 stands for normal operation, 1 stands for
standby operation.
In the line below you can define the operating status of the unit.
0 means normal operation, 1 means standby operation. as above item
➌
➐
. Delay time (zone parameter)
The evaluation of the average value will be delayed by this time.
➑. Standby units (unit parameter)
A zone, in which a sequencing shall be carried out, must contain at least one
standby unit. With the setting "1" the actual unit is defined as standby unit.
This setting defines the initial state of the sequencing and changes accor-
ding to the actual state of the sequencing.
zone 1 avgdelay 60
zone 1 unit 3 0
zone 1 unit 3 1
Operate/Zone
Config/Zone/more/more