C7000 INSTRUCTIONS fOR A/C UNITS
The corresponding commands:
➒. Maximum fan speed (nMaxZone) (zone parameter)
The adjusted speed is valid for each unit of the zone, if the standby manage-
ment is enabled and when all units are running. In case of failure of one unit
the remaining units increase their fan speed so that the total air volume flow
is kept constant.
With DFC control or enabled Ecocool function the nMaxZone speed is valid
FC mode and is initial speed in EFC mode.
➓. Maximum fan speed (SAPSM) (zone parameter)
see chapter 6.6 supply air pressure standby management.
. Supply air pressure value (zone parameter)
There are four possibilities for the setting of the supply air pressure value.
. Valid alarms (zone parameter)
With the setting "1" the corresponding alarm is defined as a valid alarm for
the zone, which entails that the unit is de-energized and the unit is registered
as defective.
deletes valid alarm 2
adds alarm 2 as valid alarm
displays list of all available alarms
0 - unit
1 - average
2 - min, smallest value in the zone
3 - max, biggest value in the zone
zone 1 nmax 85
zone 1 nmaxsapsm 40
zone 1 sapsel 0
zone 1 alarm 2 0
zone 1 alarm 2 1
zone 1 alarm h
Config/Zone/more/more