C7000 INSTRUCTIONS fOR a/C UNITS
Range GValve 1 GValve 2
Component configured
0 - 1 0 0
Output A
0 - 20 4 0
Pre-open time
0 - 255 s 30 s 30 s
Pre-opening
0 - 100 % 100% 100%
Opening setpoint
0 - 100 % 70% 70%
Minimum opening
0 - 100 % 25% 25%
Opening in standby
0 - 100 % 0% 0%
Min. opening start temp.
-20 - 50°C 0°C 0°C
Min. opening gradient
0,0 - 10,0 0,0 0,0
Control start
0 - 9,9 V 2,0 V 2,0 V
P-factor
0 - 100 40 40
I-factor
0 - 100 60 60
D-factor
0 - 100 0 0
Max. alternation
1 - 30 2% 2%
Range GE/CWValve 1 GE/CWValve 2
Component configured 0 - 1 0 0
Output A 0 - 20 2 4
Uk24mod 0 - 8 0 0
Start temperature -9,9 - 9,9 K -0,3 K 0,5 K
GE-off 0 - 100 °C 23°C 23°C
GE-off relative 0 - 9,9 K 0,0 K 0,0 K
Valve close at setpoint 0 - 1 0 0
Heating 0 - 1 0 0
Output inversion 0 - 1 0 0
Control start 0 - 9,9 V 2,0 2,0
P-factor 0 - 100 30 30
I-factor 0 - 100 1 1
D-factor 0 - 100 0 0
Valves in hydraulic circuit
GE/CW valves
G valves
CW control
Input D 0 (0 - 43)
Output D 0 (0 - 31)
Valve close at compr. 0 (0 - 1)
Valve operating mode 0 (0 - 1 - 2)
Setpoint 70% (0 - 100)
Value at switching 0% (0 - 100)
Mixmode max. value 100% (0 - 100)
100% pre-opening 0 s (0 - 255)