190 EN/06.2019/G57 © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS fOR a/C UNITS
Reheats
Range electr. reheat 1 electr. reheat 2 electr. reheat. 3
Type 1 - 2 1 1 fix 1 fix
Start 0 - 9.9 K 1.5 K 2 K 2.5 K
Stop hysteresis 0 - 9.9 K 0.5 K 0.5 K 0.5 K
Gradient 0.3 - 9.9 K 0.5 K 0.5 K 0.5 K
Component configured
0 - 1 0 0 0
Output D 0 - 31 3 4 12
Alarm input D 0 - 43 4 4 4
Alarm priority 0 - 31 0 0 0
Common alarm 0 - 1 1 1 1
Alarm delay 0 - 2550 s 4 s 4 s 4 s
Runtime 0 - 2.147.483.647 0 h 0 h 0 h
Range Hot water reh.
Type 1 - 2 1
Start 0 - 9.9 K 1.0 K
Stop hysteresis 0 - 9.9 K 0.5 K
Gradient 0.5 - 9.9 K 0.5 K
Component configured
0 - 1 0
Output D 0 - 31 4
Output A 0 - 20 7
Range Hot gas reheat
Start 0 - 9.9 1.0 K
Stop hysteresis 0 - 9.9 0.5 K
Component configured
0 - 1 0
Output D 0 - 31 4
Alarm input D 0 - 43 0
Alarm priority 0 - 31 0
Common alarm 0 - 1 0
Alarm delay 0 - 2550 s 1 s