191 © STULZ GmbH – all rights reserved EN/06.2019/G57
C7000 INSTRUCTIONS fOR A/C UNITS
Humidifiers
Dehumidifier
Range Humidifier 1 Humidifier 2 Humidifier 3
Type 1 - 2 2 2 2
Start, relative humidity 0 - 20 %r.h. 0 %r.h. 0 %r.h. 0 %r.h.
Hysteresis, relative humidity 0 - 20 %r.h. 5 %r.h. 5 %r.h. 5 %r.h.
Gradient, relative humidity 0,5 - 20 10 10 10
Start, specific humidity 0 - 20 g/kg 0 g/kg 0 g/kg 0 g/kg
Hysteresis, specific humidity 0 - 20 g/kg 1 g/kg 1 g/kg 1 g/kg
Proportional band, specific hum. 0.1 - 20 g/kg 2 g/kg 2 g/kg 2 g/kg
Component configured 0 - 1 0 0 0
Conductivity meter conf. 0 - 1 0 0 0
Output D 0 - 31 13 0 0
Output A 0 - 20 3 6 7
Alarm input D 0 - 43 6 6 6
Alarm priority 0 - 31 0 0 0
Common alarm 0 - 1 1 1 1
Alarm delay 0 - 2550 s 5 s 5 s 5 s
Alarm input D 5µS 0 - 43 0 0 0
Alarm priority 5µS 0 - 31 0 0 0
Common alarm 5µS 0 - 1 0 0 0
Alarm delay 5µS 0 - 2550 s 300 s 300 s 300 s
Alarm input D 20µS 0 - 43 6 6 6
Alarm priority 20µS 0 - 31 0 0 0
Common alarm 20µS
0 - 1 1 1 1
Alarm delay 20µS 0 - 2550 s 300 s 300 s 300 s
Runtime 0 - 2.147.483.647 0 h 0 h 0 h
Range Dehumidifier
Start, relative humidity 0 - 100 %r.h. 10 %r.h.
Hysteresis, relative humidity 0 - 30 %r.h. 5 %r.h.
Start, specific humidity 0 - 30 g/kg 0 g/kg
Hysteresis, specific humidity 0 - 30 g/kg 1 g/kg
Dehumidification stop 0 - 10 K 2 K
Dehumidif. valve conf. 0 - 1 0
Bypass valve conf. 0 - 1 0
Output D 0 - 31 5
Min water temperature -20 - 50°C 5°C
Max water temperature 0 - 100°C 14°C
Type, humidity control 0 - 2 0