28
Info
.../DIN
.../DOUT
.../AIN
.../AOUT
EN/06.2019/G57 © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS FOR A/C UNITS
* Exception: When dehumidification is carried out, the relay is not
activated.
The menu displays the number of configured sensors.
The submenus "DIN", "DOUT", "AIN", "AOUT" serve for diagnosis purposes
and display the state of each digital and analog in/output.
In the first line the inputs from 1 to 4 are displayed, in the second line the
inputs from 5 to 8 etc.
The meaning of the displayed values can be taken from the table below.
Components
IO-rawdata
Display Signification
DIN 1 Voltage present → no alarm
DOUT 1
Relay activated* → component in
service
AIN 04095
020mA, 010V corresp. to sensor
type
AOUT 04095 010V