C7000 INSTRUCTIONS fOR A/C UNITS
The corresponding commands:
For the limit value alarms "Water temperature 1 too low/too high" you can
adjust:
common alarm release (1=yes).
➍ ➑
alarm priority ➌ ➐
For the limit value alarms "Water temperature 2 too low/too high" you can
adjust:
common alarm release (1=yes).
➃ ➇
alarm priority ➂ ➆
.../Values
Water/more
You can set minimum
and maximum limit values for water temperature 1.
When the limit values are exceeded, the alarms "Water temperature 1 too low/
high" are released.
Also the alarm delays
➋ ➏ can be set in this menu.
For water temperature 2:
Minimum limit
Maximum limit
Minimum alarm delay
Maximum alarm delay
Water inlet temperature 1 Water inlet temperature 2
minalarm 5 limit -20,0
minalarm 5 delay 30
minalarm 5 dout 8
minalarm 5 common 1
maxalarm 5 limit 45,0
maxalarm 5 delay 30
maxalarm 5 dout 10
maxalarm 5 common 1
minalarm 12 limit -20,0
minalarm 12 delay 30
minalarm 12 dout 8
minalarm 12 common 1
maxalarm 12 limit 45,0
maxalarm 12 delay 30
maxalarm 12 dout 10
maxalarm 12 common 1