C7000 INSTRUCTIONS fOR A/C UNITS
The corresponding commands:
Setting of the network address only by
C7000 command:
eev 1 id 198
Components/Cooling/Valves
EEV/more
. Temperature limit for MOP control. Above this evaporation temperature the
expansion valve is not opened further.
Following menu:
. Start opening degree for the expansion valve
. Advanced start time for the expansion valve. The compressor start is delay-
ed by this time in order that the expansion valve can obtain its start opening
degree.
Alarm parameters:
Four alarms exist:
. Pressure sensor alarm,
. Temperature sensor alarm,
. Stepper motor alarm,
. Reachability alarm, Modbus connection not established or faulty.
a, a, a, a: common alarm release.
b, b, b, b: alarm priority.
NOTICE
The EEV is not configured neither in the basic setting nor in any loadde-
fault setting. If required it must be configured in this menu.
eev 1 alarmpriopress 18
eev 1 alarmpriotemp 17
eev 1 alarmpriomotor 19
eev 1 alarmpriona 10
eev 1 moptemp 23.3
eev 1 preopen 60
eev 1 pretime 15
eev 1 commonalarmpress 0
eev 1 commonalarmtemp 1
eev 1 commonalarmmotor 1
eev 1 commonalarmna 1