C7000 INSTRUCTIONS fOR a/C UNITS
The corresponding commands:
Alarm parameters:
Digital input airflow alarm
➊
Common alarm release
➋
Alarm priority ➌
Digital input filter alarm ➍
Common alarm release ➎
Alarm priority ➏
A special alarm treatment is applicated for units in which three fans are con-
figured. In case of malfunction of a fan the speed of the two remaining fans is
increased to 100%.
In case of malfunction of two fans the third fan is also switched off.
Components/Air
Fan/Alarm
fan 1 alarm 2
fan 1 commonalarm 1
fan 1 alarmprio 3
fan 1 lteralarm 6
fan 1 commonalarmfi 1
fan 1 filteralarmprio 4
Config