EasyManua.ls Logo

Sur-Gard System Five - 7.4 SG-DRL5 Static Options: 00 - 2 F

Sur-Gard System Five
155 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.0 SG-DRL5/DRL5E/DRL5-2L PSTN Line Cards
- 103 -
Nxxyy = SIA event
[00] - Output for all internal signals is SRRL protocol
SRRLLL[#AAAA|Nxxyy]
[01] - Output for all internal signals is 0RRL (Zero) protocol
0RRLLL[#AAAA|Nxxyy]
Option 044: Line card Class Field
Default (04)
00 Send "0"s in C.L.A.S.S. field of CONCOMM/RBUS packet.
01 Send Receiver Line Card Number (RRLLL) from options in C.L.A.S.S. field.
02 Send DNIS in C.L.A.S.S. field.
03 Send Caller ID in C.L.A.S.S. field.
04 Send whatever option12 Caller Source is set to in the C.L.A.S.S. field.
05 Send the convert data from the DNIS/Caller-ID (combined) Conversion table in the C.L.A.S.S. field.
Example: DNIS is: 99802
Automation:
S99802[#1234|NBA0F10]
Printer:
03 Jun 2008 08:33:33 - 03 Jun 2004-08:33:32-01/01-SG -99-802-1234--Alarm Zone
7.4 SG-DRL5 static options: 00 - 2F
NOTE: Options are displayed for the DRL5-2L. Single channel line cards only have options 1XX available to them. Options in the 2XX
range are channel 2 of the SG-DRL5-2L.
SG-DRL5 Option 101/201: Line Card Number
Default (01)
The line card Number provides a virtual identification code for each line card. Hexadecimal numbers '01' to 'FE' can be programmed in Option 101/201
to identify line cards.
SG-DRL5 Option 104/204: 2-Way Audio Activation Time
Default (00)
This option determines how long, in 10-second increments, the 2-way audio function will be active once it is initiated. At the end of this time, the line
card will hang up the line. Program a value from "01" to "FF" for 10 seconds to 2550 seconds. Three (3) minutes is the recommended length of time for
the 2-way audio activation time. To disable the 2-way audio feature, program Option 104/204 as "00".
NOTE: Enabling 2-way audio will affect NFPA 72 system loading requirements. Refer to Par. 4-5.3.2.2.2 of NFPA 72 for details. If the
alarm panel sends a listen-in code activation request and audio is enabled for this format (Option 17F/27F or 10B/20B), the receiver
will remain in 2-way voice for a period of 60 seconds even if the activation time is not programmed.
For UL Listed products, the permitted setting is 00.
SG-DRL5 Option 105/205: Pre-H.S. Duration
SG-DRL5 Default (1A)
When the line card seizes the line, it will wait the time programmed at Option 105/205; then send the first handshake. The value programmed (hex) at
this location will be multiplied by 100ms (e.g., 100ms, 200ms). The SG-DRL5 default is 0A, for 1000ms (100ms x default value).
The minimum time is 1 second. If the option is programmed with any value lower than 0A, the line card will use a 1 second delay. The maximum time
for this option is 5 seconds (option programmed for 0x32) Option value higher than 0x32 will use a 5 second delay.
SG-DRL5 Option 109/209: First Ring Length
Default (05)
In order for the line card to detect an incoming ring, the ring signal must be ON for a minimum amount of time. This option allows the user to change
the minimum amount of time the ring signal must be ON before the receiver will detect a valid ring length. The minimum ring duration allowed is 200
ms which corresponds to a value of 02 (200 ms). Values programmed will be multiplied by 100 ms. Values of 00 and 01 give a first ring length of
500ms.

Table of Contents