EasyManua.ls Logo

Sur-Gard System Five - UPS Setup

Sur-Gard System Five
155 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.0 Hardware Descriptions and Specifications
- 29 -
4.2.6 UPS setup
FIGURE 4-8: SG-System 5 UPSsupervision connection diagram
UPS LOW BAT Normally Closed
Common
UPS AC TROUBLE Normally Closed
UPS
AC In
AC Out
Input 2
Input 1
COM
IEC Power
Connector
EGND
FIGURE 4-9: I/O Terminal UPS connections
1 3 2
1. Input 1 UPS AC Failure: toggles from ground to open on failure.
2. GND Common (ground)
3. Input 2 UPS DC Failure: battery of the UPS failed (toggles from ground to open on failure)
For UL/ULC installations, use a UL listed UPS (Uninterruptible Power Supply) for protective-signaling systems and/or a listed burglary alarm power
supply, as applicable.
NOTE: UPS connection is to be made using dry contact connections provided by the UPS.
For UL and ULC installation of model SG-System 5: UPS Output 120V AC/60Hz, 5A
For ULC Installations, the equipment shall be rack mounted and energized by a permanently wired supply in accordance with C22.1, Canadian Electrical
Code, Part 1, Safety Standard for Electrical Installations, section 32.
Connection to a UPS (Uninterruptible Power Supply) with minimum 24 hour standby capability is required.
WARNING: To reduce the risk of electrical shock, the product is provided with a grounding type power supply IEC receptacle. Connect product
using an appropriate IEC cable to a grounded receptacle.

Table of Contents

Related product manuals