Appendix D: Events and Messages
- 139 -
Description/event Automation message Printer message
CPM 2 Auxiliary CPU Restore NOTE for V1.10
CPM this message may not be required as the trouble
condition is currently latching
001000[#0000|NYZ0004]
SG -01-000-0000-NYZ0004-Secondary CPM 2 Auxiliary CPU
Restore
Temp 1 Warning 001000[#0000|NKSss01] SG -01-000-0000-NKSss01-Primary CPM TEMP WARNING
Temp 1 Alarm 001000[#0000|NKAss01] SG -01-000-0000-NKAss01-TEMP 1 ALARM
Temp 1 Restore 001000[#0000|NKJss01] SG -01-000-0000-NKJss01-TEMP 1 RESTORE
Temp 2 Warning 001000[#0000|NKSss02] SG -01-000-0000-NKSss21-Primary CPM TEMP WARNING
Temp 2 Alarm 001000[#0000|NKAss02] SG -01-000-0000-NKAss02-TEMP 2 ALARM
Temp 2 Restore 001000[#0000|NKJss02] SG -01-000-0000-NKJss02-TEMP 2 RESTORE
LCD 1 Absent 001000[#0000|NAT0200] SG -01-000-0000-NAT0200-UIB 1 Cable Failed
LCD 1 Restore 001000[#0000|NAR0200] SG -01-000-0000-NAR0200-UIB 1 Cable Restored
LCD 2 Absent 001000[#0000|NAT0300] SG -01-000-0000-NAT0300-UIB 2 Cable Failed
LCD 2 Restore 001000[#0000|NAR0300] SG -01-000-0000-NAR0300-UIB 2 Cable Restored
PSU 1 Fan Failure (this is a fan spinning or not
trouble)
001000[#0000|NYP0000] SG -01-000-0000-NYP0000-PSU1 Fan Failed
PSU 1 Fan Restore 001000[#0000|NYQ0000] SG -01-000-0000-NYQ0000-PSU1 Fan Restored
PSU 2 Fan Failure (this is a fan spinning or not
trouble)
001000[#0000|NYP0001] SG -01-000-0000-NYP0001-PSU2 Fan Failed
PSU 2 Fan Restore 001000[#0000|NYQ0001] SG -01-000-0000-NYQ0001-PSU2 Fan Restored
Volatile Memory Failure 001000[#0000|NIAss00] SG -01-000-0000-NIAss00-Volatile Memory Failed
Expansion EMMC Failure 001000[#0000|NIAss01] SG -01-000-0000-NIAss01-Non Volatile Memory Failed
SD Card Failure 001000[#0000|NIAss02] SG -01-000-0000-NIAss02-SD Memory Failed
SD 90% Full 001000[#0000|NJLss02] SG -01-000-0000-NJLss02-SD Memory 90% full
SD 100% Full 001000[#0000|NJOss02] SG -01-000-0000-NJOss02-SD Memory 100% full
SD Card Formatted - From the console 001000[#0000|NRTss02] SG -01-000-0000-NRTss02-SD Memory FORMATTED
Firmware Update Start 001001[#0000|NMIss00] SG -01-001-0000-NMIss00- Firmware Update Initiated
Firmware Update Failed 001001[#0000|NMIss01] SG -00-001-0000-NMIss01- Firmware Update Failed
CPM 1 RTC Battery Trouble Restore 001000[#0000|NYR0110] SG -01-000-0000-NYR0110-Primary CPM RTC Battery Restored
CPM 1 RTC Battery Trouble 001000[#0000|NYT0110] SG -01-000-0000-NYT0110- Primary CPM RTC Battery Failed
CPM 2 RTC Battery Trouble restore 001000[#0000|NYR0210]
SG -01-000-0000-NYR0210-Secondary CPM RTC Battery
Restored
CPM 2 RTC Battery Trouble 001000[#0000|NYT0210] SG -01-000-0000-NYT0210- Secondary CPM RTC Battery Failed
USB 1 Active 001001[#0000|NRCss01] SG -00-001-0000-NRCss01- USB port 1 Active
USB 1 Inactive 001001[#0000|NROss01] SG -00-001-0000-NROss01- USB port 1 Inactive
USB 2 Active 001001[#0000|NRCss02] SG -00-001-0000-NRCss02- USB port 2 Active
USB 2 Inactive 001001[#0000|NROss02] SG -00-001-0000-NROss02- USB port 2 Inactive
USB 3 Active 001001[#0000|NRCss03] SG -00-001-0000-NRCss03- USB port 3 Active
USB 3 Inactive 001001[#0000|NROss03] SG -00-001-0000-NROss03- USB port 3 Inactive
Printer test Not Applicable SG -01-000-0000-Printer Test Message
COLDBOOT was performed by User via Console 001000[#0000|NYE0100] SG -01-000-0000-NYE0100-COLDBOOT by CONSOLE
COLDBOOT was performed by User via hardware
reset
001000[#0000|NYE0100] SG -01-000-0000-NYE0100-COLDBOOT by Hardware
COLDBOOT was performed by User via LCD 001000[#0000|NYE0100] SG -01-000-0000-NYE0100-COLDBOOT by LCD
User performed manual automation test message
from LCD.
001000[#0000|NRX0000] No Printer message
CPM Decommissioned 001000[#0000|NSCssoo] SG -01-000-0000-NSCssoo-Decommissioned
CPM Recommissioned Used when Re-com-
missioned from Console, Push button or SD Card
Format.
001000[#0000|NRRssoo*
vX.XX.XXX.XXX*]
SG -01-000-0000-NRRssoo- Recommissioned vX.XX.XXX.XXX
AHS Size Mismatch AHS tables are of different
sizes on the 2 CPMs
001000[#0000|NYUss01] SG -01-000-0000-NYUss01-AHS License Mismatch