8-137
Index Subindex Name
Data
Type
Access
PDO
Mapping
Saving
to
EEPROM
Default Value
Supported mode
Unit
Param
eter
No.
Lower
Limit
Upper Limit
All PP PV PT HM IP CSP CSV CST
1800h
Transmit PDO1 Communication Parameter
0 Number of entries USINT RO No No 5
- - - -
1 COB-ID used by PDO UDINT RW No No
0x00000180 +
Node-ID
- - - -
2 Transmission type USINT RW No No 255
- - - -
3 inhibit time UINT RW No No 0x0064
- - - -
4 reserved USINT RW No No 0x00
- - - -
5 event timer UINT RW No No 0x0064
- - - -
1801h
Transmit PDO2 Communication Parameter
0 Number of entries USINT RO No No 5
- - - -
1 COB-ID used by PDO UDINT RW No No
0x80000280 +
Node-ID
- - - -
2 Transmission type USINT RW No No 255
- - - -
3 inhibit time UINT RW No No 0x0064
- - - -
4 reserved USINT RW No No 0x00
- - - -
5 event timer UINT RW No No 0x0064
- - - -
1802h
Transmit PDO2 Communication Parameter
0 Number of entries USINT RO No No 5
- - - -
1 COB-ID used by PDO UDINT RW No No
0x80000380 +
Node-ID
- - - -
2 Transmission type USINT RW No No 255
- - - -
3 inhibit time UINT RW No No 0x0064
- - - -
4 reserved USINT RW No No 0x00
- - - -
5 event timer UINT RW No No 0x0064
- - - -
1803h
Transmit PDO3 Communication Parameter
0 Number of entries USINT RO No No 5
- - - -
1 COB-ID used by PDO UDINT RW No No
0x80000480 +
Node-ID
- - - -