24 Fire Panel IRIS - Installation Manual
- The device maintains day and nighttime working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The nighttime mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
3.2.2.12.5 - FTX-P1 (Photoelectric Smoke sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
2251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and nighttime working modes. Each of these are assigned different times of filtra
-
tion of the FIRE signal. The nighttime mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
3.2.2.12.6 – 6500 (Linear smoke sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
2251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and nighttime working modes. Each of these are assigned different times of filtra
-
tion of the FIRE signal. The nighttime mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
- The device can be tested by covering the reflector, depending on the selected alarm level. As a result a
FIRE signal is generated to the respective zone. In the case of complete blockage of the reflector a “BEAM
BLOCKAGE” message is generated. If there are any reflective objects in the path of the detector a “SIGNAL
OVER RANGE” message is generated.
3.2.2.12.7 - 5251EM (Temperature sensor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and nighttime working modes. Each of these are assigned different times of filtra
-
tion of the FIRE signal. The nighttime mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
3.2.2.12.8 - 5251TEM (Temperature sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
5251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.