Fire Panel IRIS - Installation Manual 27
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
3.2.2.12.19 - M500KAC (Call point)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device). On a correct adjustment of the type, after activation
of a Call Point is generated an alarm signal to the relevant device.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
3.2.2.12.20 - M512ME (Zone monitor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
3.2.2.12.21 - EMA24 & DBS24 (Loop sounders)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the output.
- Introduce the name of the device – 40 digits.
Important: Every device can be enabled or disabled. When disabled a “LOOP DEVICE DISA-
BLED” message is generated to the respective zone. No signals will be perceived from a
disabled device. Device disabling does not terminate after a RESET command.