4 Fire Panel IRIS - Installation Manual
1.2.1 General Technical Specifications
• Loops - 1 or 2 loop versions as standard
• Up to 99 detectors and 99 modules per loop
• Zones - 96 displayed zones
• Inputs - 4 programmable for volt-free Normal Open contact
• Monitored relay outputs – 4 (Sounder, Fire, Fault and Fire Protection)
• Non monitored relay outputs – 4 programmable, 230V/ 10A
• Display – 320x240 CSTN graphic display (118.8mm X 89.38mm) with a touch panel
• Real time clock
• Up to 128 programmable Inputs/Outputs per panel
• Comprehensive day/night mode facility
• Simple Windows graphical configuration utility via Ethernet or USB
• Simple Http monitoring utility
• Loop less panel option (repeater)
• Thermal printer (optional)
• Digital communicator (optional)
• Flush mounting enclosure
• Multi-language support
• Easy software update
Absolutely compatible with the requirements of EN54-2/4
1.2.2 Structure
Maximum configuration:
- Main PCB
- Power Source
- LED-indication
- Main Board
- 20 Relays Expander Module
- 2 Loop Controllers
- Modem
- Heat Printer
1.2.3 Environment
- Ambient Temperature: -5˚C up to +50˚C
- Relative Humidity: up to 95% (without condense)
- Storage Temperature: -10˚C up to +60˚C
- Weight (without the battery): 6kg.
1.2.4 Electrical Specifications
Earth connection
The earth connection has to be realized in accordance with the rules for the electrical safety with the total
resistance in the circuit lower than 10Ω. It is mandatory to connect the main power supply cable to the middle
input of the fire panel terminal - see §2.2.7 Power Source.
Main power supply
In normal operating conditions the fire panel is powered from the mains voltage line. In case of mains volt-
age line loss the fire panel is equipped with one rechargable battery. The characteristics of the main power
supply are as follows:
- Mail Power Supply: ~230V ±10%
- Frequency: 50/ 60Hz
- Electrical output: 1A
!
ATTENTION: Do not instal the fire panel near power electromagnetic fields (radio equip-
ments, electric motors, etc.)!
Minimum configuration:
- Main PCB
- Power Supply

Table of Contents