46 Fire Panel IRIS - Installation Manual
6. APPENDIX
Appendix A
Possible error messages:
LOOP DEVICE TYPE ERROR
A different than the expected type of device has been detected
at the address.
LOOP DEVICE FAULT
The device does not respond (lost or damaged).
LOOP DEVICE DOUBLE ADDRESS
More than one device with the same address in the loop.
PREALARM Fire signal from detector in 2DEVICES zone.
EVACUATE Activated Call Point or EVACUATE button on the panel.
INPUT FAULT
Fault in loop device input.
OUTPUT FAULT
Fault in loop device output.
LOOP DEVICE DISABLED
Loop device has been disabled.
CHAMBER FAULT Fault in the detector.
CLEAN ME NOW Dirty detector chamber.
TEST FIRE Fire signal from tested detector.
SIGNAL BLOCKAGE Signal blockage in linear detector.
HI SIGNAL Too high a signal in linear detector.
EARTH FAULT
Resistive connection between some signals and earth < 10k.
BATTERY LOW Low battery.
CHARGER FAULT
Fault in the charging device.
BATTERY LOSS Loss of electric battery supply.
AC LOSS Loss of mains supply.
SOUNDER FAULT
Fault at sounder output (short-circuit or interruption).
FAULT ROUTING FAULT
Fault at problem output (short-circuit or interruption).
FIRE BRIGADE FAULT Fault at fire output (short-circuit or interruption).
FIRE PROTECTION FAULT
Fire protection fault (short-circuit or interruption).
AUX24V FAULT
Short-circuit.
AUX12V FAULT
Short-circuit.
PERIPHERY DEVICE FAULT
The device does not respond (lost or damaged).
PERIPHERY DEVICE TYPE ERROR A different than the expected type of device has been detected
at the address.
EXTERNAL POWER SUPPLY FAULT
External power supply fault (low battery, loss of battery,
charger fault, loss of mains or earth leak).
EXTERNAL POWER SUPPLY LOSS Loss of external power supply.
ZONE DISABLED The zone has been disabled.
TEST ZONE
The zone is in test mode.
SOUNDER DISABLED The sounders have been disabled.
FIRE BRIGADE DISABLED The fire output has been disabled.
FIRE PROTECTION DISABLED The fire protection has been disabled.
FAULT DISABLED
The fault output has been disabled.
PERIPHERY DEVICE NEW
New periphery devices have been detected.
LOOP DEVICE NEW
New loop devices have been detected.
LOOP SHORT
Short-circuit in the loop.
LOOP BREAK
Interrupted loop.
ALARM Fire signal from detector.